Customization: | Available |
---|---|
Type: | Cold Shrink |
Material: | Silicone Rubber |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Indoor Termination | Cross Section (mm²) |
||
Cold Shrink Type | Pre-moulded Type | 8.7/15(17.5)kV | 12/20(24)kV |
HCLN-20-S-1 | HCYN-20-1 | 25-50 | 25 |
HCLN-20-S-2 | HCYN-20-2 | 70-95 | 35-70 |
HCLN-20-S-3 | HCYN-20-3 | 120-150 | 95-120 |
HCLN-20-S-4 | HCYN-20-4 | 185-240 | 150-185 |
HCLN-20-S-5 | HCYN-20-5 | 300-400 | 240-400 |
HCLN-20-S-6 | HCYN-20-6 | 500-630 | 500-630 |
Rated Voltage | 8.7/15(17.5)kV | 12/20(24)kV |
Running Temperature | 17.5kV | 24kV |
AC Withstand Voltage and DC Withstand Voltage | 39kV 5min, or 35kV, 15min, no flashover, no breakdown | 54kV, 5min, or 48kV, 15min, no flashover, no breakdown |
Partial Discharge | 15kV, PD≤5pC | 20kV, PD≤5pC |
Impulse Voltage Test | 95kV, ±10 times | 125kV, ±10 times |
Short Circuit Thermal Stability (Conductor) | 24kA, 2s twice, no visible damage | 25kA, 2s twice, no visible damage |
Short Circuit Dynamic Stability | 83kA, not less than 10ms, no visible damage | 63A, not less than 10ms, no visible damage |
Constant Voltage Load Cycle | apply voltage 1.25 u0 to conductor and heat to(90-95)ºC heat for 5h and cool for 3h, total 3 times | |
Salt Spray Test | 1.25U0 1000h, no flashover, no breakdown, trip not more than 3 times, no obvious damage | |
Humidity Test | 1.25U0 300h, no flashover, no breakdown, trip not more than 3 times, no obvious damage | |
Long-time Running Temperature | -40ºC to 95ºC | |
Short Circuit Temperature | 250ºC, lasting time less than 5s | |
Cable Accessories Conductor Material | copper, aluminum, copper&aluminum |