Customization: | Available |
---|---|
Certification: | ISO9001, ISO14001, Ohsas18000, Type Test, etc |
Shell Material: | Steel |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
L Module | P Module | V Module | |||
Load switch | Fuse unit | Breaker unit | |||
Rated Voltage | kV | 12 | 12 | 12 | |
Rated Current | A | 630 | 200 | 630 | |
Power frequency withstand voltage 1 min |
Phase to earth/ phase to phase |
kV | 42 | 42 | 42 |
Insulating distance | kV | 48 | 48 | 48 | |
Impulse withstand voltage | Phase to earth/ phase to phase |
kV | 95 | 75 | |
Insulating distance | kV | 125 | 85 | ||
Rated closed loop breaking current | A | 630 | |||
Rated cable-charging breaking current | A | 30 | |||
Rated breaking inductive current | A | ||||
Rated short-time withstand current 4s | kA | 20 | 20/25 | ||
Rated peak withstand current | kA | 50 | 50 | ||
Rated transfer current | A | 1700 | |||
Rated short circuit breaking current | kA | 20 | |||
Rated short circuit making current | kA | 50 | |||
Rated short circuit breaking times | times | ||||
Rated short circuit making times (load switch/grounding switch) | times | 5/5 | 30 | ||
Rated current breaking times | times | >100 | |||
Machine operation times (load switch/ground switch) | times | 5000/2000 | 5000/2000 | 30000 |
Normal environment condition | SF6 Gas pressure | Under 20 c 0.4 bar | |
Environment temperature | Year leakage rate | 0.25 per year | |
Max temperature | +50ºC | Protection class | |
Max temperature (24 hours average) | +35ºC | SF6 air chamber | IP67 |
Min temperature | -40ºC | Switchgear shell | IP3X |
Humidity | |||
Max average relative humidity 24 hours | ≤95% | ||
Altitude | ≤1000 meter |