Customization: | Available |
---|---|
Type: | Cold Shrink |
Material: | Silicone Rubber |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Indoor Termination | Conductor Cross Section (mm²) |
||
Cold Shrink Type | Premoulded Type | 18/30(36)kV | 26/35(40.5)kV |
HCLN-35-1 | HCYN-35-1 | 50-120 | 50-95 |
HCLN-35-2 | HCYN-35-2 | 150-240 | 120-185 |
HCLN-35-3 | HCYN-35-3 | 300-630 | 240-400 |
HCLN-35-4 | HCYN-35-4 | 500-630 |
Rated Voltage | 18/30(36)kV | 26/35(40.5)kV |
Running Temperature | 36kV | 40.5kv |
AC Withstand Voltage and DC Withstand Voltage | 81kV,5min, or 72kV, 15min, no flashover, no breakdown | 117kV, 5min or 104kV, 15 min no flashover, no breakdown |
Partial Discharge | 30kV, PD≤5pC | 45kV, PD≤5pC |
Impulse Voltage Test | 170kV, ±10 times | 200kV, ±10 times |
Short Circuit Thermal Stability (Conductor) | 23kA, 2s twice, no visible damage | 25kA 2s twice, no visible damage |
Short Circuit Dynamic Stability | 83kA, not less than 10ms, no visible damage | 88kA, not less than 10ms, no visible damage |
Constant Voltage Load Cycle | apply voltage 1.25U0 to conductor and heat to(90-95)ºC heat for 5h and cool for 3h, total 3 times | |
Salt Spray Test | 1.25U0 1000h, no flashover, no breakdown, trip not more than 3 times, no obvious damage | |
Humidity Test | 1.25U0 300h, no flashover, no breakdown, trip not more than 3 times, no obvious damage | |
Long-time Running Temperature | -40ºC to 95ºC | |
Short Circuit Temperature | 250ºC, lasting time less than 5s | |
Cable Accessories Conductor Material | copper, aluminum, copper&aluminum |