18/30(36)kV External Busbar and Separable Connectors to combine switchgears
Applied to 18/30(36)kV voltage class switchgears and combine several switchgears, realize insulation for top extension and deliver current.
Advantage
1. Screen method: coating and injection with good insulation.
2. Any length of busbar is available by customization.
3. Easy to instal and less cost.
Technical Data
NO. |
Item |
36kV External Busbar and Connectors |
1 |
Rated Voltage(U0/U) |
18/30kV |
2 |
Max Voltage(Um) |
36kV |
3 |
Rated Frequency |
50Hz |
4 |
Rated Current |
1250A |
5 |
Temperature Rise of Rated Current Conductor below |
50K |
6 |
Rated Thermal Stability Current (4s) |
25kA |
7 |
Rated Dynamic Current (0.3s) |
63kA |
8 |
Rated Insulation Level |
|
|
Partial Discharge |
39.6kV, Q ≤10pC |
|
Power-frequency Withstand Voltage (1 min) |
81kV |
|
Lightning Impulse Withstand Voltage (1.2/50ms) |
±170kV |
9 |
Connection Way |
Conductive Bolt Tight Compression |
10 |
Copper Conductor |
T2Y(Purity>99.9%) |
11 |
DC Resistance |
<20μΩ |
12 |
Type |
C Type |
13 |
Model NO. |
HCPS-MX-36/1250 HCPS-T-36/1250 HCPS-+-36/1250 |
Workshop
Test Room
Shenzhen Hifuture Electric Co., Ltd. is committed to professional power distribution grid equipment and integrated solutions.
More details about our company and products, please kindly visit our website: hifuture.en.made-in-china.com.